BWR type Gland: Bwr Cable Gland with saperate Locking Ring. Bwr Cable Gland suitable for SWA cables, Positive armour locking, increased mechanical strength and effective earth continuity. For indor and dry application.
Entry Threads: Metric thread available as standard. Other thread forms e.g BS Conduit, BSP, NPT, and PG available on request.
Accessories: Shrouds, Lock nuts and Earth Tags Available.
Manufactured as per BS 6121 PT -1. 1989 From Brass as standard material.
|
Bwr Gland Size
|
Entry Thread
|
Cable Dimensions
|
Armour Wire Diameter
|
Across Corner Diameter
|
Item Code
|
|
Diameter mm
|
length mm
|
A (max)
|
B (max)
|
|
20/16
|
20
|
10
|
8.60
|
13.4
|
0.90
|
24.4
|
30161
|
|
20S
|
20
|
10
|
11.6
|
15.9
|
0.90-1.25
|
27.5
|
30205
|
|
20
|
20
|
10
|
13.9
|
20.8
|
0.90-1.25
|
31.6
|
30201
|
|
25S
|
25
|
10
|
17.1
|
23.5
|
1.25-1.60
|
36.0
|
30255
|
|
25
|
25
|
10
|
19.9
|
27.4
|
1.25-1.60
|
39.0
|
30251
|
|
32
|
32
|
10
|
26.2
|
33.5
|
1.60-2.00
|
47.0
|
30321
|
|
40S
|
40
|
15
|
30.2
|
38.2
|
1.60-2.00
|
55.0
|
30405
|
|
40
|
40
|
15
|
32.2
|
40.0
|
1.60-2.00
|
57.0
|
30401
|
|
50S
|
50
|
15
|
38.1
|
46.5
|
2.00-2.50
|
67.0
|
30505
|
|
50
|
50
|
15
|
44.0
|
53.0
|
2.00-2.50
|
69.0
|
30501
|
|
63S
|
63
|
15
|
50.0
|
61.5
|
2.00-2.50
|
79.0
|
30635
|
|
63
|
63
|
15
|
55.8
|
67.0
|
2.00-2.50
|
85.0
|
30631
|
|
75S
|
75
|
15
|
61.8
|
72.0
|
2.50-3.20
|
95.0
|
30755
|
|
75
|
75
|
15
|
67.8
|
78.0
|
2.50-3.20
|
101.0
|
30751
|
|
88/90
|
88/90
|
15
|
80.0
|
91.0
|
2.50-3.20
|
120.0
|
30901
|
|
100
|
100
|
25
|
90.0
|
90.0
|
3.20
|
136.0
|
301001
|
|
110
|
110
|
25
|
99.0
|
99.0
|
3.20
|
145.0
|
301101
|
|